PART ID · KLE-004 · Verified asset

Kinedizer LE Burner

KINEDIZER® LE · 10" model · Maxon (Honeywell)

Serial
MX-KLE10-2023-04719
Installed
Aug 14, 2023
Site
Industria Machina Demo Plant · Cell B-3
On asset
CleanSwitch RTO · CS-1235
Component
Burner Assembly · Main combustion chamber
Last inspected
Apr 22, 2026

Manuals

PUBLIC

Manufacturer documentation, datasheets, and installation guides for this exact part. Available to anyone with the QR.

Specifications

PUBLIC

Operating envelope distilled from the manufacturer datasheet. Useful for sanity-checking field readings against design intent.

Max capacity (n=1.3 low NOx)
24.3 MBtu/h
Min capacity
1.215 MBtu/h
Turndown
20:1
Air flow at max
5,050 scfm
Flame length @ n=1.3
9 ft
Flame diameter @ n=1.3
4 ft
Natural gas inlet ΔP
75 "wc
Weight
662 lbs
Max chamber temperature
2,000 °F
Combustion air temp
Ambient to 660 °F
Fuel
Natural gas, propane, other gaseous fuels
Burner tip material
AISI 310 (1.4541)
Refractory block
Castable, 50% SiO₂ / 45% Al₂O₃

Maintenance reports

TECHNICIAN

Field service history for this asset. Each entry links to the full report with photos, observations, and corrective actions.

  • R-2026-04-22-KLE004 Apr 22, 2026 · M. Reyes

    Burner tip showing early-stage spalling on outboard quadrant. Block sleeve seal nominal.

    WARNING
  • R-2026-01-15-KLE004 Jan 15, 2026 · A. Whitfield

    Quarterly: no abnormalities. Pilot light-off pressure 0.08"wc, within spec. Combustion air ΔP 30"wc.

    GOOD
  • R-2025-10-08-KLE004 Oct 8, 2025 · M. Reyes

    Gas inlet test connection seal leaking 0.4"wc — replaced gasket and re-torqued to 18 ft·lb. Confirmed leak-tight after rebuild.

    CRITICAL
  • R-2025-07-02-KLE004 Jul 2, 2025 · J. Park

    Annual: stainless burner parts inspected, no discoloration beyond expected oxide layer. Block intact.

    GOOD

Vision scanning

ENGINEER

Walk the part. Photograph each checklist step on your phone. Luthier runs a vision model trained on this fleet's history and produces a structured report with annotated findings — typically in under 90 seconds per checklist item.